Checking and updating IEC 60870-5-103 points - Grid automation - Engineering Manual - REC615 Grid Automation Protection and Control - RER615 Grid Automation Protection and Control - Relion 615 series - 2.0 - IEC - ANSI - 28.04.2023

REC615 and RER615 Engineering Manual

If IEC 60870-5-103 is used, the migrated IEC 60870-5-103 point list should for most part correspond to the configuration made in the old IED.
  1. Check the point list and verify that all the point types correspond to the old configuration and IEC 60870-5-103 master.
    • Indications
    • Measurands
  2. If some points have different attributes, adjust them in the Communication Management tool.
  3. Change the possible changed point addresses to match the master address by using a user-defined address instead of the default address.
  4. Adjust possible missing points points in IEC 60870-5-103 master configuration.