Checking and updating DNP3 points - Grid automation - Engineering Manual - REC615 Grid Automation Protection and Control - RER615 Grid Automation Protection and Control - Relion 615 series - 2.0 - IEC - ANSI - 28.04.2023
REC615 and RER615 Engineering Manual
If DNP3 is used, the migrated DNP3 point list should for most part correspond to the configuration made in the old IED. - Check the point list and verify that all the point types correspond to the old configuration and DNP3 master.
- Analog input objects
- Binary input objects
- Binary output objects
- Counter objects
- Double bit indication objects
- Analog output objects
- If some points have different point addresses or other mapping attributes, adjust them in the Communication Management tool.
- Add the possible missing points in the migrated configuration by taking them back to use in the Communication Management tool.