The DNP3 parameters can be accessed with PCM600 or via the LHMI path
.Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
5=off |
Operation Off / On |
||
Port |
1=COM 1 2=COM 2 3=Ethernet - TCP 1 4=Ethernet TCP +UDP 1 |
3=Ethernet - TCP 1 |
Communication interface selection |
||
Unit address |
1...65519 |
1 |
1 |
DNP unit address |
|
Master address |
1...65519 |
1 |
3 |
DNP master and UR address |
|
Mapping select |
1...2 |
1 |
1 |
Mapping select |
|
ClientIP |
0.0.0.0 |
IP address of client |
|||
TCP port |
20000...65535 |
1 |
20000 |
TCP Port used on ethernet communication |
|
TCP write authority |
0=No clients 1=Reg. clients 2=All clients |
2=All clients |
0=no client controls allowed; 1=Controls allowed by registered clients; 2=Controls allowed by all clients |
||
Link keep-alive |
0...65535 |
s |
1 |
0 |
Link keep-alive interval for DNP |
Validate master addr |
1=Disable 2=Enable |
1=Disable |
Validate master address on receive |
||
Self address |
1=Disable 2=Enable |
2=Enable |
Support self address query function |
||
Need time interval |
0...65535 |
min |
1 |
30 |
Period to set IIN need time bit |
Time format |
0=UTC 1=Local |
1=Local |
UTC or local. Coordinate with master. |
||
CROB select timeout |
1...65535 |
s |
1 |
10 |
Control Relay Output Block select timeout |
Data link confirm |
0=Never 1=Only Multiframe 2=Always |
0=Never |
Data link confirm mode |
||
Data link confirm TO |
100...65535 |
ms |
1 |
3000 |
Data link confirm timeout |
Data link retries |
0...65535 |
1 |
3 |
Data link retries count |
|
Data link Rx to Tx delay |
0...255 |
ms |
1 |
0 |
Turnaround transmission delay |
Data link inter char delay |
0...20 |
char |
1 |
4 |
Inter character delay for incoming messages |
Data link frame length |
50...292 |
bytes |
1 |
292 |
Data link maximum frame length |
App layer confirm |
1=Disable 2=Enable |
1=Disable |
Application layer confirm mode |
||
App confirm TO |
100...65535 |
ms |
1 |
5000 |
Application layer confirm and UR timeout |
App layer fragment |
50...2048 |
bytes |
1 |
2048 |
Application layer fragment size |
UR mode |
1=Disable 2=Enable |
1=Disable |
Unsolicited responses mode |
||
UR retries |
0...65535 |
1 |
3 |
Unsolicited retries before switching to UR offline mode |
|
UR TO |
0...65535 |
ms |
1 |
5000 |
Unsolicited response timeout |
UR offline interval |
0...65535 |
min |
1 |
15 |
Unsolicited offline interval |
UR Class 1 Min events |
0...999 |
1 |
2 |
Min number of class 1 events to generate UR |
|
UR Class 1 TO |
0...65535 |
ms |
1 |
50 |
Max holding time for class 1 events to generate UR |
UR Class 2 Min events |
0...999 |
1 |
2 |
Min number of class 2 events to generate UR |
|
UR Class 2 TO |
0...65535 |
ms |
1 |
50 |
Max holding time for class 2 events to generate UR |
UR Class 3 Min events |
0...999 |
1 |
2 |
Min number of class 3 events to generate UR |
|
UR Class 3 TO |
0...65535 |
ms |
1 |
50 |
Max holding time for class 3 events to generate UR |
Legacy master UR |
1=Disable 2=Enable |
1=Disable |
Legacy DNP master unsolicited mode support. When enabled relay does not send initial unsolicited message. |
||
Legacy master SBO |
1=Disable 2=Enable |
1=Disable |
Legacy DNP Master SBO sequence number relax enable |
||
Default Var Obj 01 |
1=1:BI 2=2:BI&status |
1=1:BI |
1=BI; 2=BI with status. |
||
Default Var Obj 02 |
1=1:BI event 2=2:BI event&time |
2=2:BI event&time |
1=BI event; 2=BI event with time. |
||
Default Var Obj 03 |
1=1:DBI 2=2:DBI&status |
1=1:DBI |
1=DBI; 2=DBI with status. |
||
Default Var Obj 04 |
1=1:DBI event 2=2:DBI event&time |
2=2:DBI event&time |
1=DBI event; 2=DBI event with time. |
||
Default Var Obj 20 |
1=1:32bit Cnt 2=2:16bit Cnt 5=5:32bit Cnt noflag 6=6:16bit Cnt noflag |
2=2:16bit Cnt |
1=32 bit counter; 2=16 bit counter; 5=32 bit counter without flag; 6=16 bit counter without flag. |
||
Default Var Obj 21 |
1=1:32bit FrzCnt 2=2:16bit FrzCnt 5=5:32bit FrzCnt&time 6=6:16bit FrzCnt&time 9=9:32bit FrzCnt noflag 10=10:16bit FrzCnt noflag |
6=6:16bit FrzCnt&time |
1=32 bit frz counter; 2=16 bit frz counter; 5=32 bit frz counter with time; 6=16 bit frz counter with time; 9=32 bit frz counter without flag;10=16 bit frz counter without flag. |
||
Default Var Obj 22 |
1=1:32bit Cnt evt 2=2:16bit Cnt evt 5=5:32bit Cnt evt&time 6=6:16bit Cnt evt&time |
6=6:16bit Cnt evt&time |
1=32 bit counter event; 2=16 bit counter event; 5=32 bit counter event with time; 6=16 bit counter event with time. |
||
Default Var Obj 23 |
1=1:32bit FrzCnt evt 2=2:16bit FrzCnt evt 5=5:32bit FrzCnt evt&time 6=6:16bit FrzCnt evt&time |
6=6:16bit FrzCnt evt&time |
1=32 bit frz counter event; 2=16 bit frz counter event; 5=32 bit frz counter event with time; 6=16 bit frz counter event with time. |
||
Default Var Obj 30 |
1=1:32bit AI 2=2:16bit AI 3=3:32bit AI noflag 4=4:16bit AI noflag 5=5:AI float 6=6:AI double |
5=5:AI float |
1=32 bit AI; 2=16 bit AI; 3=32 bit AI without flag; 4=16 bit AI without flag; 5=AI float; 6=AI double. |
||
Default Var Obj 32 |
1=1:32bit AI evt 2=2:16bit AI evt 3=3:32bit AI evt&time 4=4:16bit AI evt&time 5=5: float AI evt 6=6:double AI evt 7=7:float AI evt&time 8=8:double AI evt&time |
7=7:float AI evt&time |
1=32 bit AI event; 2=16 bit AI event; 3=32 bit AI event with time; 4=16 bit AI event with time; 5=float AI event; 6=double AI event; 7=float AI event with time; 8=double AI event with time. |
||
Default Var Obj 40 |
1=1:32bit AO 2=2:16bit AO 3=3:AO float 4=4:AO double |
2=2:16bit AO |
1=32 bit AO; 2=16 bit AO; 3=AO float; 4=AO double. |
||
Default Var Obj 42 |
1=1:32bit AO evt 2=2:16bit AO evt 3=3:32bit AO evt&time 4=4:16bit AO evt&time 5=5:float AO evt 6=6:double AO evt 7=7:float AO evt&time 8=8:double AO evt&time |
4=4:16bit AO evt&time |
1=32 bit AO event; 2=16 bit AO event; 3=32 bit AO event with time; 4=16 bit AO event with time; 5=float AO event; 6=double AO event; 7=float AO event with time; 8=double AO event with time. |