Diagnostic communication counters - Grid automation - DNP3 Communication Manual - REC615 Grid Automation Protection and Control - RER615 Grid Automation Protection and Control - 2.0 - IEC - ANSI - 27.04.2023

REC615 and RER615 DNP3 Communication Protocol Manual

Protocol instance n dependent diagnostic communication counters are provided in the protection relay. These counters can be accessed via Monitoring > Communication > DNP3.0 > DNP3.0n.

Table 1. Diagnostic communication counters
Diagnostic counter Description
Received frames Total amount of received DNP3 frames
Transmitted frames Total amount of transmitted DNP3 frames
Physical errors Total amount of Physical layer errors noticed
Link errors Total amount of Link layer errors noticed
Transport errors Total amount of Transport layer errors noticed
Mapping errors Total amount of Protocol mapping errors noticed
Status Shows the value "True" if the TCP/IP or serial instance is active. This means that a DNP3 client has connected to the TCP socket and DNP3 messages are received regularly at least within <Link keep-alive> second interval or faster. In all other cases this value shows "False".
Reset counters True = Reset all diagnostic counters

For non-activated instances n, no communication diagnostic values are shown by the HMI. Diagnostic counter values are initially set to “-1” to indicate that no messages have yet been processed by the active instance. As soon as a message is received or transmitted, the counters initialize to “0”.

In a serial-bus troubleshooting case, if no DNP3 diagnostic counter is running, the COMn serial driver settings and driver diagnostic counters should be checked.