REC615 Modification Sales Guideline

  • Computer with latest released PCM600 and REC615 connectivity package versions. It is recommended to use the latest REC615 connectivity package available in the Update Manager.
  • Up-to-date projects in PCM600 containing all the relays under modification
  • Modification Sales package delivered as a .zip file
  • Ethernet cable
  • Replace the existing product labels with the new ones (two copies) included in the delivery.
    Note: If the delivery contains material for the modification of several relays, check the correct label based on the serial number of each relay under modification.
  • The delivery includes two modification files, package with latest firmware and license and package with only license. If the customer chooses the package that includes only license, then customer needs to check that the firmware has the correct connectivity level. It is must to keep the relay firmware up to date.
    Note: Check the latest relay firmware from ABB Data Care.
  • Adequate access rights to perform software update for the relay
CAUTION: As the relay is in the factory default configuration state after the license update process, ensure that the current configuration of the relay under modification is available in the PCM600 project. If needed, select Read from IED before starting the update process.
Note: ENGINEER access rights are needed to update configuration.
Note: ADMINISTRATOR access rights are needed to manage user access rights.
Note: System update rights are needed to update the relay firmware. (Refer to table Default roles-to-rights in REC615 Cyber Security Deployment Guideline)