Technical specifications can be changed without notification. For information on the supported mobile data speed, see the mobile data reference guide.
|
Description |
Value |
|---|---|
|
Width × Height × Depth |
108 × 45 × 175 mm (without antenna) |
|
Weight |
590...610 g |
|
Description |
Value |
|
|---|---|---|
|
Processor environment |
Processor |
32 bit RISC |
|
Memory |
128 MB Flash |
|
|
128 MB RAM |
||
|
Power |
Power supply |
12…48 VDC, limited (<240 VA) power source that fulfills the requirements of standard IEC 60950-1 or IEC 62368-1 |
|
Power consumption |
ARR600A3261NA: <7W or <66W if DC output loaded ARR600A3262NA: <7W or <36W if DC output loaded |
|
|
Other |
Internal clock |
Real time |
|
Approvals |
CE |
|
|
Environmental conditions |
Temperature range |
-30...+70°C (operating) |
|
-40...+85°C (storage) |
||
|
Humidity |
5...85% RH (non condensing) |
|
|
Protection class |
IP30 |
|
|
Master protocol |
Slave protocol |
|---|---|
|
IEC 60870-5-104 |
IEC 60870-5-101 |
|
IEC 60870-5-104 |
Modbus RTU/ASCII, Modbus TCP |
|
Modbus TCP |
Modbus RTU/ASCII |
|
TCP/IP, UDP/IP (DNP3) |
Serial gateway - serial port data stream (such as DNP3) |
|
Master protocol |
|---|
|
IEC 60870-5-104 |
|
Modbus TCP |
|
SNMP |
|
Description |
Value |
|
|---|---|---|
|
Ethernet ports |
Ethernet/LAN |
10/100 Base-T. Shielded RJ-45 |
|
1.5 kV isolation transformer |
||
|
Ethernet IEEE 802-3, 802-2 |
||
|
Serial ports |
Serial 1/Console |
RS-232 DTE |
|
Male DB-9 connector |
||
|
IEC 60870-5-101 protocol support |
||
|
Full serial and modem signals |
||
|
300...460 800 bps |
||
|
Data bits: 7 or 8 |
||
|
Stop bits: 1 or 2 |
||
|
Parity: None, Even, Odd |
||
|
Flow control: None, RTS/CTS |
||
|
Protection: 15 kV ESD and short circuit |
||
|
Console: RS-232, 19200 bps, 8 data bits, 1 stop bit, no parity (8N1) |
||
|
Serial 2 |
RS-232 DTE, RS-422, RS-485 (selectable) |
|
|
Male DB-9 connector |
||
|
IEC 60870-5-101 protocol support |
||
|
Full serial and modem signals |
||
|
300...460 800 bps |
||
|
Data bits: 7 or 8 |
||
|
Stop bits: 1 or 2 |
||
|
Parity: None, Even, Odd |
||
|
Flow control: None, RTS/CTS |
||
|
Protection: 15 kV ESD and short circuit |
|
Description |
Reference |
|
|---|---|---|
|
Emission tests according to the test specification IEC 61850-3 (Edition 2.0 2013-12) |
Radiated disturbance |
CISPR 16-2-3 |
|
Conducted disturbance |
CISPR 16-2-1 |
|
|
Immunity tests according to the test specification IEC 61850-3 (Edition 2.0 2013-12) |
Electrostatic discharge (ESD) |
EN 61000-4-2 (2008-12) |
|
Radiated radiofrequency electromagnetic field |
EN 61000-4-3 (2006-02) |
|
|
Electrical fast transient (EFT) |
EN 61000-4-4 (2012-04) |
|
|
Surge |
EN 61000-4-5 (2005-11) |
|
|
Conducted radiofrequency electromagnetic field |
EN 61000-4-6 (2008-10) |
|
|
Power frequency magnetic field |
EN 61000-4-8 (2009-09) |
|
Description |
Reference |
|---|---|
|
Directive |
RoHS directive 2002/95/EC |
|
REACH directive 2006/1907/EC |