Serial port 2 can be configured to multiple serial formats (RS-232/422/485). The default is RS-232.

Figure 1. Application serial port
image/svg+xml
Table 1. Application serial port pinout (RS-232)

PIN

Function

1

DCD

2

RXD

3

TXD

4

DTR

5

GND

6

DSR

7

RTS

8

CTS

9

RI

Table 2. Application serial port configuration

Parameter

Value

Baud rate

300...460800 bps

Data bits

8

Parity

No parity

Stop bits

1

Flow control

CTS/RTS

By default, all DIP switches are set to the 0 position (RS-232 mode). DIP switches 2...4 apply only when DIP switch 1 is set to differential mode (RS-485/RS-422).

Table 3. DIP switches

DIP switch

Mode

State

Description

1

RS-232 or differential

0 = RS-232, 1 =

RS-485 and RS-422

Selects the serial port operation mode

2

DUPLEX

0 = FULL, 1 = HALF

Selects between RS-422 full-duplex (4- wire) and RS-485 half- duplex (2-wire) differential modes

3

BIASING

0 = OFF, 1 = ON

Enables RS-422 biasing on pins 2 and 8

4

TERMINATION

0 = OFF, 1 = ON

Enables RS-422 termination on pins 2 and 8

Note: If biasing and/or termination is required for the RS-485 half-duplex (2-wire) mode, enable RS-422 biasing/termination with DIP switches and manually connect pins 2-7 and 3-8 together at the application port (RS-2).
Warning: Do not connect RS-422 or RS-485 cables to a serial port configured to the RS-232 mode. This could damage the port and the connected equipment.
Table 4. Application serial port pinouts in RS-422/485 modes

PIN

RS-422 full-duplex (4-wire)

RS-485 half-duplex (2-wire)

1

-

-

2

RXD positive (in)

-

3

TXD negative (out)

TXD/RXD negative (out/in)

4

-

-

5

GND

GND

6

-

-

7

TXD positive (out)

TXD/RXD positive (out/in)

8

RXD negative (in)

-

9

-

-