ARR600 User Manual

Table 1. Modbus register map for IO-1 (8DI+2DO)

Function code (Hex)

Function

Address range

Number of registers

Modicon notation

Properties

1 (0x01)

Read Coils

0…1

2

00001…00002

Read digital outputs

2 (0x02)

Read Discrete Inputs

0…7

8

10001…10008

Read digital inputs

3 (0x03)

Read Multiple Holding Registers

0…7

8

40001…40008

Read input counters

5 (0x05)

Write Single Coil

0…1

2

00001…00002

Write digital output

6 (0x06)

Write Single Holding Register

0…7

8

40001…40008

Clear input counter

15 (0x0F)

Write Multiple Coils

0…1

2

00001…00002

Write digital outputs

16 (0x10)

Write Multiple Holding Registers

0…7

8

40001…40008

Clear input counters

Table 2. Modbus register map for IO-2 (6DI+4DO+2AI)

Function code (Hex)

Function

Address range

Number of registers

Modicon notation

Properties

1 (0x01)

Read Coils

0…3

4

00001…00004

Read digital outputs

2 (0x02)

Read Discrete Inputs

0…5

6

10001…10006

Read digital inputs

3 (0x03)

Read Multiple Holding Registers

0…5

6

40001…40006

Read input counters

4 (0x04)

Read Input Registers

0…1

2

30001…30002

Read analog inputs. For analog values, the returned value is calculated like this: value = (raw value - offset) ·multiply·

100. Offset and multiply are taken from the calibration file.

5 (0x05)

Write Single Coil

0…3

4

00001…00004

Write digital output

6 (0x06)

Write Single Holding Register

0…5

6

40001…40006

Clear input counter

15 (0x0F)

Write Multiple Coils

0…3

4

00001…00004

Write digital outputs

16 (0x10)

Write Multiple Holding Registers

0…5

6

40001…40006

Clear input counters