DC output - Grid automation - User Manual - ARR600 Wireless I/O Gateway - Arctic series - 3.4 - IEC - ANSI - 21.06.2023

ARR600 User Manual

The input voltage to the power supply connector is circulated back to the I/O connector of the device. This DC output can be used, for example, together with digital outputs in order to simplify external circuitry and wiring.

Table 1. DC outputs’ maximum current ratings

Description

Value

ARR600A3262NA

0.66A, at ambient temperature +20°C

0.41A, at ambient temperature +55°C

0.32A, at ambient temperature +70°C

ARR600A3261NA

1.28A, at ambient temperature +20°C

0.83A, at ambient temperature +55°C

0.63A, at ambient temperature +70°C