Console/serial port 1 - Grid automation - User Manual - ARR600 Wireless I/O Gateway - Arctic series - 3.4 - IEC - ANSI - 21.06.2023

ARR600 User Manual

The console switch enables or disables console access. When the switch is in the right position, serial port 1 is in the serial port mode, and when it is in the left position, serial port 1 is in the console mode.

The console switch is located below the serial port 1 connector. Turn off power from the device before toggling the console switch, as the switch position is read during the boot sequence only. The baud rate is fixed to 115200 bps when the port is configured in the serial console mode.

Figure 1. Console/RS1 port connector
image/svg+xml
Table 1. Console/RS1 port pinout

PIN

Function

1

DCD

2

RXD

3

TXD

4

DTR

5

GND

6

DSR

7

RTS

8

CTS

9

RI

Table 2. Console/RS1 port configuration

Parameter

Value

Baud rate

300...230400 (console 115200) bps

Data bits

8

Parity

No parity

Stop bits

1

Flow control

No flow control