Configuring the network master to serial slaves mode - Grid automation - User Manual - ARR600 Wireless I/O Gateway - Arctic series - 3.4 - IEC - ANSI - 21.06.2023

ARR600 User Manual

  1. In the left pane, under Serial Port and I/O, click Modbus Gateway (RSx).
  2. Set Enable Modbus gateway to Yes.
  3. Set Gateway mode to Network master to serial slaves.
  4. Set the parameters under Serial settings, Protocols, Framing, Exceptions and Network server settings as the network and the Modbus master and slaves require.
  5. Click Submit to save the settings.
  6. Restart the device.