Technical data (ARM600 hardware variants) - Grid automation - User Manual - ARM600 M2M Gateway - Arctic series - 5.0 - IEC - ANSI - 21.10.2022

ARM600 User Manual

Table 1. Dimensions

Description

Standard edition

Enterprise edition

Height × Width × Depth

4x 3.5” chassis
  • 42.8 × 434.0 × 596 mm (without bezel)
  • 1.67 × 17.09 × 23.5 in
8x 2.5" chassis
  • 42.8 × 434.0 × 545 mm (without bezel)
  • 1.67 × 17.09 × 21.5 in
Table 2. Hardware

Description

Standard edition

Enterprise edition

Processor environment

Processor

Intel Pentium

Intel Xeon

Memory

8 GB UDIMM

32 GB UDIMM

HDD

480 GB SSD SATA

6Gbps

2.5in hot-plug

Dual, 480 GB SSD

SATA 6Gbps

2.5in hot-plug

Power supply

Single power supply 350 W

Dual, hot-plug, redundant power supply (2 ×), 550 W

Casing

Metal, 19" rack mountable (1U)

Metal, 19" rack mountable (1U)

Approvals

Global CB Scheme, CE, FCC

Global CB Scheme, CE, FCC

Environmental conditions

Temperature: Continuous operation (for altitude less than 950 m or 3117 ft)

10...35°C (50...95°F)

10...35°C (50...95°F)

Relative humidity: operating

10...80% relative humidity with 29°C (84.2°F) maximum dew point

10...80% relative humidity with 29°C (84.2°F) maximum dew point

Table 3. Standard and Enterprise editions

Description

Value

Operating voltage 1

100...240 V AC, autoranging, 50/60 Hz

Temperature

Continuous operation (for altitudes less than 950 m or 3,117 ft)

10...35°C (50...95°F) with no direct sunlight on the equipment

Storage

-40...65°C (-40...149°F)

Relative humidity

Operating

10...80% relative humidity with 29°C (84.2°F) maximum dew point

Storage

5...95% relative humidity with 33°C (91°F) maximum dew point

The atmosphere must be non-condensing at all times.

Maximum vibration

Operating

0.26 Grms at 5...350 Hz (operation orientation)

Storage

1.88 Grms at 10...500 Hz for 15 min (all six sides tested)

Maximum shock

Operating

One pulse on each side of the system of 71 G for up to 2 ms

Storage

Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms

Maximum altitude

Operating

30,482,000 m (100,006,560 ft)

Storage

12,000 m (39,370 ft)

Operating altitude de-rating

Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft)

Table 4. Ordering data

Description

Standard edition

ARM600C2500NA

Enterprise edition

ARM600C2505NA

Ethernet ports

2

4

Power supply

single

dual

HDD

single

dual

RAID

no

yes

CPU type

Intel Pentium

Intel Xeon

RAM

8 GB

32 GB

Max Arctic connections

300

2000 2

Size

1U 19"

1U 19"

1 Also designed to be connected to IT power systems with a phase-to-phase voltage that does not exceed 230 V
2 With the hardware listed in Table 2.