Device function type - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - IEC 60870-5-103 Communication Manual - 620 series Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series IEC 60870-5-103 Communication Protocol Manual

The IEC 60870-5-103 standard requires that an IED is identified as a certain Device type. The standard has only the following single functional device types:
  • 128 distance protection
  • 160 overcurrent protection device
  • 176 transformer differential protection
  • 192 line differential protection
Since the IEDs are multifunctional, the Device type is set to the private function type value 9 as default. However, if this definition would cause incompatibility with some client systems, the definition can be changed through the DevFunType n parameter.

The value in DevFunType n is automatically assigned to all IEC 60870-5-103 data points that have their function type defined as 0. The user has to assure that no similar IEC 60870-5-103 point definitions already exist with the same function type and information number.