Communication link - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - IEC 60870-5-103 Communication Manual - 620 series Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series IEC 60870-5-103 Communication Protocol Manual

The IEC 60870-5-103 protocol can only operate on a serial communication link. The standard defines serial data characteristics.

Table 1. Serial data characteristics
Parameter Value
Com speed 9600 or 19200 bauds
Data bits 8
Parity Even
Start bits 1
Stop bits 1

Depending on the IED model and variant, the serial communication cards can host one or several serial channels. The IEC 60870-5-103 protocol can operate in up to two instances and therefore supporting two IEC 60870-5-103 masters in parallel. The two instances will share the same point configuration, but each instance has its own independent Class 1 event buffer. Instances can also have different Class 2 measurand frames. Separate link setting parameters exist for both instances. Setting parameters have the suffixes 1 or 2 depending on the instance.

A function block represents the IEC 60870-5-103 protocol on the IED’s application configuration level. The block is named I3CLPRT1 or I3CLPRT2, depending on which of the two protocol instances is in use.

Figure 1. Function block
image/svg+xmlI3CLPRTEC_FRZSTATUS

By default, Instance 1 is active in the IED, but needs to be set “On” by the Operation parameter. For additional clients, an instance has to be activated by dragging a function block to the configuration in the Application Configuration tool of the PCM600.