Circuit breaker control model - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - IEC 60870-5-103 Communication Manual - 620 series Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series IEC 60870-5-103 Communication Protocol Manual

Circuit breaker can only be controlled with DIRECT ON/OFF commands. This is due to the limitations in the IEC 60870-5-103 standard. In case the IED’s internal (IEC 61850) circuit breaker control model is set to Select-Before-Operate, the IEC 60870-5-103 stack will internally emulate both SELECT and OPERATE commands toward the circuit breaker. To the IEC 60870-5-103 client the control operation always appears to be DIRECT.