LD0.TR2PTDF1 Stabilized and instantaneous differential protection for two-winding transformers (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series DNP3 Point List Manual

Table 1. LD0.TR2PTDF1 Stabilized and instantaneous differential protection for two-winding transformers (1)
IEC 61850 name SA name Description Value
LD0.TR2PTRC1
.Op.general OPERATE General operate 1=Operate
.Op.phsA OPR_A Phs A operate 1=Operate
.Op.phsB OPR_B Phs B operate 1=Operate
.Op.phsC OPR_C Phs C operate 1=Operate
LD0.TR2LPDIF1
.BlkWavSt.general BLKDWAV Waveform block, general 1=Blocking
.BlkWavSt.phsA BLKDWAV_A Waveform block, phs A 1=Blocking
.BlkWavSt.phsB BLKDWAV_B Waveform block, phs B 1=Blocking
.BlkWavSt.phsC BLKDWAV_C Waveform block, phs C 1=Blocking
.Blk2HSt.general BLKD2H 2nd harmonic res. block, general 1=Blocking
.Blk2HSt.phsA BLKD2H_A 2nd harmonic res. block, phs A 1=Blocking
.Blk2HSt.phsB BLKD2H_B 2nd harmonic res. block, phs B 1=Blocking
.Blk2HSt.phsC BLKD2H_C 2nd harmonic res. block, phs C 1=Blocking
.Blk5HSt.general BLKD5H 5th harmonic res. block, general 1=Blocking
.Blk5HSt.phsA BLKD5H_A 5th harmonic res. block, phs A 1=Blocking
.Blk5HSt.phsB BLKD5H_B 5th harmonic res. block, phs B 1=Blocking
.Blk5HSt.phsC BLKD5H_C 5th harmonic res. block, phs C 1=Blocking