LD0.SSCBR3 Circuit-breaker condition monitoring (3) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 31.05.2023

620 series DNP3 Point List Manual

Table 1. LD0.SSCBR3 Circuit-breaker condition monitoring (3)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.SSCBR3
.OpCntRs.stVal NO_OPR Number of CB operations 0...99999 R 0,99999,0,99999
.InaTmdCnt.stVal INA_DAYS CB inactive days 0...9999 R 0,9999,0,9999
.OpTmOpn.mag T_TRV_OP Opening travel time 0…60000 [ms] R 0,60000,0,60000
.OpTmCls.mag T_TRV_CL Closing travel time 0…60000 [ms] R 0,60000,0,60000
LD0.SSOPM3
.TmsSprCha.mag T_SPR_CHR Spring charging time 0...99.99 [s] R 0,100,0,10000
LD0.SPH1SCBR3
.AccmAPwr.mag IPOW_A Phs A acc. currents power 0…30000 R 0,30000,0,30000
.RmnNumOp.stVal CB_LIFE_A Phs A remaining life -99999...99999 R -99999,99999,-99999,99999
LD0.SPH2SCBR3
.AccmAPwr.mag IPOW_B Phs B acc. currents power 0…30000 R 0,30000,0,30000
.RmnNumOp.stVal CB_LIFE_B Phs B remaining life -99999...99999 R -99999,99999,-99999,99999
LD0.SPH3SCBR3
.AccmAPwr.mag IPOW_C Phs C acc. currents power 0…30000 R 0,30000,0,30000
.RmnNumOp.stVal CB_LIFE_C Phs C remaining life -99999...99999 R -99999,99999,-99999,99999