LD0.SSCBR2 Circuit-breaker condition monitoring (2) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 31.05.2023

620 series DNP3 Point List Manual

Table 1. LD0.SSCBR2 Circuit-breaker condition monitoring (2)
IEC 61850 name SA name Description Values
LD0.SSCBR2
.OpCntAlm.stVal OPR_ALM CB operations alarm 1=Alarm
.OpnAlm.stVal TRV_T_OP_ALM Cls travel time alarm 1=Alarm
.ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
.OpCntLO.stVal OPR_LO CB operations lockout 1=Lockout
.LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
.APwrAlm.stVal IPOW_ALM Iyt alarm 1=Alarm
.APwrLO.stVal IPOW_LO Iyt lockout 1=Lockout
.RmnNumOpAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
LD0.SSIMG2
.InsAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
.InsBlk.stVal PRES_LO Low pressure lockout 1=Lockout
LD0.SSOPM2
.SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 1=Alarm