LD0.SCEFRFLO1 Fault locator (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023

620 series DNP3 Point List Manual

Table 1. LD0.SCEFRFLO1 Fault locator (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.FLO1RFRC1
.FltDiskm.mag Fault distance 0…3000.000 [km] 0,3000,0,3000000
.FltLoop.stVal Fault loop 0…7 0,7,0,7
.FltPtR.mag Fault point resistance 0...1000000.0 [ohm] 0,1000000,0,10000000
.FltR.mag Fault loop resistance 0...1000000.0 [ohm] 0,1000000,0,10000000
.FltX.mag Fault loop reactance 0...1000000.0 [ohm] 0,1000000,0,10000000
.PhReact.mag Fault phase reactance 0...1000000.0 [ohm] 0,1000000,0,10000000
.RatFltALod.mag Fault to load current ratio 0...60000.00 0,60000,0,6000000
.EqDisLod.mag Estim. equivalent load distance 0.00...1.00 0,1,0,100
.PhGndCapac.mag Estim. PE line capacitive reactance 0.0...1000000. 0 [ohm] 0,1000000,0,10000000
.FltDisQ.stVal Fault distance quality 0...511 0,512,0,512