LD0.PEMMXU1 Three-phase power and energy measurement (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023

620 series DNP3 Point List Manual

Table 1. LD0.PEMMXU1 Three-phase power and energy measurement (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.PEMMXU1
.TotW.instMag P-kW Total active power -/+999999.9 R multiplied by 10
.TotVA.instMag S-kVA Total apparent power -/+999999.9 R multiplied by 10
.TotVAr.instMag Q-kVAr Total reactive power -/+999999.9 R multiplied by 10
.TotPF.instMag PF Average power factor -1.00…1.00 R -1,1,-100,100
LD0.PEAVMMXU1
.TotW.mag Total active power demand -/+999999.9 R multiplied by 10
.TotVAr.mag Total apparent power demand -/+999999.9 R multiplied by 10
.TotVA.mag Total reactive power demand -/+999999.9 R multiplied by 10
.TotPF.mag Average power factor demand -1.00…1.00 R -1,1,-100,100
LD0.PEMAMMXU1
.TotW.mag Total active power demand max. -/+999999.9 R multiplied by 10
.TotVAr.mag Total apparent power demand max. -/+999999.9 R multiplied by 10
.TotVA.mag Total reactive power demand max. -/+999999.9 R multiplied by 10
LD0.PEMIMMXU1
.TotW.mag Total active power demand min. -/+999999.9 R multiplied by 10
.TotVAr.mag Total apparent power demand min. -/+999999.9 R multiplied by 10
.TotVA.mag Total reactive power demand min. -/+999999.9 R multiplied by 10