LD0.MPDIF1 Stabilized and instantaneous differential protection for machines (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series DNP3 Point List Manual

Table 1. LD0.MPDIF1 Stabilized and instantaneous differential protection for machines (1)
IEC 61850 name SA name Description Value
LD0.MPTRC1
.Op.general OPERATE General operate 1=Operate
.Op.phsA Phs A operate 1=Operate
.Op.phsB Phs B operate 1=Operate
.Op.phsC Phs C operate 1=Operate
LD0.MLPDIF1
.BlkIntnSt.general INT_BLKD Internal block 1=Blocked
.BlkIntnSt.phsA INT_BLKD_A Internal block phs A 1=Blocked
.BlkIntnSt.phsB INT_BLKD_B Internal block phs B 1=Blocked
.BlkIntnSt.phsC INT_BLKD_C Internal block phs C 1=Blocked