LD0.FLTRFRC1 Fault recorder (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 31.05.2023

620 series DNP3 Point List Manual

Table 1. LD0.FLTRFRC1 Fault recorder (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.FLTRFRC1
Values only for reading 1
.OpTm.t Captured time (year) 0...3000 0,3000,0,3000
.OpTm.t Captured time (month) 1...12 1,12,1,12
.OpTm.t Captured time (day) 1…31 1,31,1,31
.OpTm.t Captured time (hour) 0…23 0,23,2,23
.OpTm.t Captured time (minute) 0…59 0,59,0,59
.OpTm.t Captured time (second) 0…59 0,59,0,59
.OpTm.t Captured time (msec) 0…999 0,999,0,999
Event updated values 2
.OpCnt.stVal Fault record number 0...999999 0,999999,0,999999
.ProFcn.stVal Protection function -32767...32768 -32768,32767,-32768,32767
.Hz.mag Frequency 30.00...80.00 [Hz] 30,80,3000,8000
.StrDur.mag Start duration 0…100.00 [%] 0,100,0,10000
.StrOpTm.mag Operate time 0.000...999999 .999 [s] 0,10000000,0,10000000
.FltPtR.mag Fault reactance 0...1000000.00 [ohm] 0,1000000,0,1000000
.FltDiskm.mag Fault distance 0.00...3000.00 [pu] 0,3000,0,300000
.ActSetGr.stVal Active setting group 1...6 1,6,1,6
.ShotPntr.stVal AR Shot pointer 1...7 1,7,1,7
.Max50DifAA.mag Max. diff. current phs A 0.000...80.000 [pu] 0,80,0,8000
.Max50DifAB.mag Max. diff. current phs B 0.000...80.000 [pu] 0,80,0,8000
.Max50DifAC.mag Max. diff. current phs C 0.000...80.000 [pu] 0,80,0,8000
.Max50RstAA.mag Max. bias current phs A 0.000...50.000 [pu] 0,50,0,5000
.Max50RstAB.mag Max. bias current phs B 0.000...50.000 [pu] 0,50,0,5000
.Max50RstAC.mag Max. bias current phs C 0.000...50.000 [pu] 0,50,0,5000
.DifAPhsA.mag Diff. current phs A 0.000...80.000 [pu] 0,80,0,8000
.DifAPhsB.mag Diff. current phs B 0.000...80.000 [pu] 0,80,0,8000
.DifAPhsC.mag Diff. current phs C 0.000...80.000 [pu] 0,80,0,8000
.RstAPhsA.mag Bias current phs A 0.000...50.000 [pu] 0,50,0,5000
.RstAPhsB.mag Bias current phs B 0.000...50.000 [pu] 0,50,0,5000
.RstAPhsC.mag Bias current phs C 0.000...50.000 [pu] 0,50,0,5000
.DifARes.mag Diff. current Io 0.000...80.000 [pu] 0,80,0,8000
.RstARes.mag Bias current Io 0.000...50.000 [pu] 0,50,0,5000
.Max50APhsA1.mag Max. current phs A(1) 0.000...50.000 [xIn] 0,50,0,5000
.Max50APhsB1.mag Max. current phs B(1) 0.000...50.000 [xIn] 0,50,0,5000
.Max50APhsC1.mag Max. current phs C(1) 0.000...50.000 [xIn] 0,50,0,5000
.Max50ARes1.mag Max. current Io(1) 0.000...50.000 [xIn] 0,50,0,5000
.APhsA1.mag Current phs A(1) 0.000...50.000 [xIn] 0,50,0,5000
.APhsB1.mag Current phs B(1) 0.000...50.000 [xIn] 0,50,0,5000
.APhsC1.mag Current phs C(1) 0.000...50.000 [xIn] 0,50,0,5000
.ARes1.mag Current Io(1) 0.000...50.000 [xIn] 0,50,0,5000
.AResClc1.mag Current Io-Calc(1) 0.000...50.000 [xIn] 0,50,0,5000
.APsSeq1.mag Current Ps-Seq(1) 0.000...50.000 [xIn] 0,50,0,5000
.ANgSeq1.mag Current Ng-Seq(1) 0.000...50.000 [xIn] 0,50,0,5000
.APhsA2.mag Current phs A(2) 0.000...50.000 [xIn] 0,50,0,5000
.APhsB2.mag Current phs B(2) 0.000...50.000 [xIn] 0,50,0,5000
.APhsC2.mag Current phs C(2) 0.000...50.000 [xIn] 0,50,0,5000
.ARes2.mag Current Io(2) 0.000...50.000 [xIn] 0,50,0,5000
.AResClc2.mag Current Io-Calc(2) 0.000...50.000 [xIn] 0,50,0,5000
.APsSeq2.mag Current Ps-Seq(2) 0.000...50.000 [xIn] 0,50,0,5000
.ANgSeq2.mag Current Ng-Seq(2) 0.000...50.000 [xIn] 0,50,0,5000
.PhVPhsA1.mag Voltage phs A(1) 0.000...4.000 [xUn] 0,4,0,4000
.PhVPhsB1.mag Voltage phs B(1) 0.000...4.000 [xUn] 0,4,0,4000
.PhVPhsC1.mag Voltage phs C(1) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsAB1.mag Voltage phs AB(1) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsBC1.mag Voltage phs BC(1) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsCA1.mag Voltage phs CA(1) 0.000...4.000 [xUn] 0,4,0,4000
.VRes1.mag Voltage Uo(1) 0.000...4.000 [xUn] 0,4,0,4000
.VZro1.mag Voltage Zro-Seq(1) 0.000...4.000 [xUn] 0,4,0,4000
.VPsSeq1.mag Voltage Ps-Seq(1) 0.000...4.000 [xUn] 0,4,0,4000
.VNgSeq1.mag Voltage Ng-Seq(1) 0.000...4.000 [xUn] 0,4,0,4000
.PhVPhsA2.mag Voltage phs A(2) 0.000...4.000 [xUn] 0,4,0,4000
.PhVPhsB2.mag Voltage phs B(2) 0.000...4.000 [xUn] 0,4,0,4000
.PhVPhsC2.mag Voltage phs C(2) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsAB2.mag Voltage phs AB(2) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsBC2.mag Voltage phs BC(2) 0.000...4.000 [xUn] 0,4,0,4000
.PPVPhsCA2.mag Voltage phs CA(2) 0.000...4.000 [xUn] 0,4,0,4000
.VRes2.mag Voltage Uo(2) 0.000...4.000 [xUn] 0,4,0,4000
.VZro2.mag Voltage Zro-Seq(2) 0.000...4.000 [xUn] 0,4,0,4000
.VPsSeq2.mag Voltage Ps-Seq(2) 0.000...4.000 [xUn] 0,4,0,4000
.VNgSeq2.mag Voltage Ng-Seq(2) 0.000...4.000 [xUn] 0,4,0,4000
.MaxTmpRl.mag PTTR thermal level 0.00...99.99 0,99.99,0,9999
.AMaxNgPs.mag PDNSPTOC1 ratio I2/I1 0.00...999.99 [%] 0,999.99,0,99999
.DifANAngVN1.mag. Angle Uo-Io(1) -180.00...180.0 0 deg -180,180,-18000,18000
.DifAAAngVBC1.mag. Angle UBC-IA(1) -180.00...180.0 0 deg -180,180,-18000,18000
.DifABAngVCA1.mag Angle UCA-IB(1) -180.00...180.0 0 deg -180,180,-18000,18000
.DifACAngVAB1.mag Angle UAB-IC(1) -180.00...180.0 0 deg -180,180,-18000,18000
.DifANAngVN2.mag. Angle Uo-Io(2) -180.00...180.0 0 deg -180,180,-18000,18000
.DifAAAngVBC2.mag. Angle UBC-IA(2) -180.00...180.0 0 deg -180,180,-18000,18000
.DifABAngVCA2.mag Angle UCA-IB(2) -180.00...180.0 0 deg -180,180,-18000,18000
.DifACAngVAB2.mag Angle UAB-IC(2) -180.00...180.0 0 deg -180,180,-18000,18000
.HzRteChg.mag Frequency gradient -10.00...10.00 [Hz/s] -10,10,-1000,1000
.CondNeut.mag Conductance Yo -1000.00...100 0.00 [mS] -1000,1000,-100000,100000
.SusNeut.mag Susceptance Yo -1000.00...100 0.00 [mS] -1000,1000,-100000,100000
.PPLoopRis.mag Fault loop resistance -1000.00...100 0.00 [ohm] -1000.00,1000.00,-100000,1 00000
.PPLoopReact.mag Fault loop reactance -1000.00...100 0.00 [ohm] -1000.00,1000.00,-100000,1 00000
.CBClrTm.mag Breaker clear time 0.000...3.000 [s] 0,3,0,3000
1 When reading out fault record values on demand, DNP3 cannot give timestamps for data objects, meaning the timestamps for the moment the objects were recorded. Instead, the timetag of the fault record is available for reading in seven regular DNP3 analog objects.
2 If fault record values are received as DNP3 events when they are recorded, the object timestamps, that is, the fault record timestamps, are given in the DNP3 event messages.