LD0.DARREC1 Autoreclosing (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023

620 series DNP3 Point List Manual

Table 1. LD0.DARREC1 Autoreclosing (1)
IEC 61850 name SA name Description Values
LD0.DARREC1
.PrgRec1.stVal INPRO_1 AR 1st reclose 1=In progress
.PrgRec2.stVal INPRO_2 AR 2nd reclose 1=In progress
.PrgRec3.stVal INPRO_3 AR 3rd reclose 1=In progress
.PrgRec4.stVal INPRO_4 AR 4th reclose 1=In progress
.PrgRec5.stVal INPRO_5 AR 5th reclose 1=In progress
.PrgRec.stVal INPRO AR in progress 1=In progress
.CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
.AutoRecOn.stVal AR_ON Autoreclose ON/OFF 1=ON
.LO.stVal LOCKED Lockout status 1=Lockout
.UnsRec.stVal UNSUC_RECL Reclose fail status 1=Failed
.InInhRec.stVal INHIBIT_RECL Inhibit reclose 1=Inhibit
.InBlkThm.stVal – Thermal block (status) 1=Block
.RdyRec.stVal READY Ready reclose status 1=Ready
.ActRec.stVal ACTIVE Active reclose status 1=Active
.SucRec.stVal SUC_RECL Successful reclose 1=Successful
.PrgDsr.stVal DISCR_INPRO Discrimination time in p. 1=In progress
.PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
.FrqOpAlm.stVal FRQ_OP_ALM Frequent operation alarm 1=Alarm
.RclTmStr.stVal – Reclaim time started 1=Started
.ProCrd.stVal – Protection coordination 1=In progress
.OpCls.general CLOSE_CB Operate (close XCBR) 1=Close CB
.OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
.UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
.WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal