LD0.CMMXU1 Three-phase current measurement (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023

620 series DNP3 Point List Manual

Table 1. LD0.CMMXU1 Three-phase current measurement (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.CMMXU1 Phase-to-ground current
.A.phsA.instCVal.mag IL1-A Phs A magnitude 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsB.instCVal.mag IL2-A Phs B magnitude 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsC.instCVal.mag IL3-A Phs C magnitude 0.00...50.00 [xIn] R 0,50,0,5000
LD0.CAVMMXU1
.A.phsA.cVal.mag I_DMD_A Phs A demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsB.cVal.mag I_DMD_B Phs B demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsC.cVal.mag I_DMD_C Phs C demand value 0.00...50.00 [xIn] R 0,50,0,5000
LD0.CMAMMXU1
.A.phsA.cVal.mag Max demand IL1 Phs A max. demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsB.cVal.mag Max demand IL2 Phs B max. demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsC.cVal.mag Max demand IL3 Phs C max. demand value 0.00...50.00 [xIn] R 0,50,0,5000
LD0.CMIMMXU1
.A.phsA.cVal.mag Min demand IL1 Phs A min. demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsB.cVal.mag Min demand IL2 Phs B min. demand value 0.00...50.00 [xIn] R 0,50,0,5000
.A.phsC.cVal.mag Min demand IL3 Phs C min. demand value 0.00...50.00 [xIn] R 0,50,0,5000