LD0.CMMXU1 Three-phase current measurement (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023
620 series DNP3 Point List Manual
Table 1. LD0.CMMXU1 Three-phase current measurement (1)
| IEC 61850 name |
SA name |
Description |
Values |
S |
Arg 1,2,3,4 |
| LD0.CMMXU1 |
|
Phase-to-ground current |
|
|
|
| .A.phsA.instCVal.mag |
IL1-A |
Phs A magnitude |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsB.instCVal.mag |
IL2-A |
Phs B magnitude |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsC.instCVal.mag |
IL3-A |
Phs C magnitude |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| LD0.CAVMMXU1 |
|
|
|
|
|
| .A.phsA.cVal.mag |
I_DMD_A |
Phs A demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsB.cVal.mag |
I_DMD_B |
Phs B demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsC.cVal.mag |
I_DMD_C |
Phs C demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| LD0.CMAMMXU1 |
|
|
|
|
|
| .A.phsA.cVal.mag |
Max demand IL1 |
Phs A max. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsB.cVal.mag |
Max demand IL2 |
Phs B max. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsC.cVal.mag |
Max demand IL3 |
Phs C max. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| LD0.CMIMMXU1 |
|
|
|
|
|
| .A.phsA.cVal.mag |
Min demand IL1 |
Phs A min. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsB.cVal.mag |
Min demand IL2 |
Phs B min. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |
| .A.phsC.cVal.mag |
Min demand IL3 |
Phs C min. demand value |
0.00...50.00 [xIn] |
R |
0,50,0,5000 |