Functions, codes and symbols - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - 2.0 FP1 IEC - IEC - 31.05.2023

620 series DNP3 Point List Manual

All available functions are listed in the table. All of them may not be applicable to all products.

Table 1. Functions included in the relays
Function IEC 61850 IEC 60617 ANSI
Protection
Three-phase non-directional overcurrent protection, low stage PHLPTOC1 3I> (1) 51P-1 (1)
PHLPTOC2 3I> (2) 51P-1 (2)
Three-phase non-directional overcurrent protection, high stage PHHPTOC1 3I>> (1) 51P-2 (1)
PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1)
PHIPTOC2 3I>>> (2) 50P/51P (2)
Three-phase directional overcurrent protection, low stage DPHLPDOC1 3I> -> (1) 67-1 (1)
DPHLPDOC2 3I> -> (2) 67-1 (2)
Three-phase directional overcurrent protection, high stage DPHHPDOC1 3I>> -> (1) 67-2 (1)
DPHHPDOC2 3I>> -> (2) 67-2 (2)
Three-phase voltage-dependent overcurrent protection PHPVOC1 3I(U)> (1) 51V (1)
PHPVOC2 3I(U)> (2) 51V (2)
Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)
EFLPTOC2 Io> (2) 51N-1 (2)
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
EFHPTOC2 Io>> (2) 51N-2 (2)
Non-directional earth-fault protection, instantaneous stage EFIPTOC1 Io>>> (1) 50N/51N (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
DEFLPDEF2 Io> -> (2) 67N-1 (2)
DEFLPDEF3 Io> -> (3) 67N-1 (3)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Admittance-based earth-fault protection EFPADM1 Yo> -> (1) 21YN (1)
EFPADM2 Yo> -> (2) 21YN (2)
EFPADM3 Yo> -> (3) 21YN (3)
Wattmetric-based earth-fault protection WPWDE1 Po> -> (1) 32N (1)
WPWDE2 Po> -> (2) 32N (2)
WPWDE3 Po> -> (3) 32N (3)
Multifrequency admittance-based earth-fault protection MFADPSDE1 Io> -> Y (1) 67YN (1)
Transient/intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
Harmonics-based earth-fault protection HAEFPTOC1 Io>HA (1) 51NHA (1)
Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46 (1)
NSPTOC2 I2> (2) 46 (2)
Phase discontinuity protection PDNSPTOC1 I2/I1> (1) 46PD (1)
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)
ROVPTOV2 Uo> (2) 59G (2)
ROVPTOV3 Uo> (3) 59G (3)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
PHPTUV2 3U< (2) 27 (2)
PHPTUV3 3U< (3) 27 (3)
PHPTUV4 3U< (4) 27 (4)
Single-phase undervoltage protection, secondary side PHAPTUV1 U_A< (1) 27_A (1)
Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)
PHPTOV2 3U> (2) 59 (2)
PHPTOV3 3U> (3) 59 (3)
Single-phase overvoltage protection, secondary side PHAPTOV1 U_A> (1) 59_A (1)
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)
PSPTUV2 U1< (2) 47U+ (2)
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)
NSPTOV2 U2> (2) 47O- (2)
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)
FRPFRQ2 f>/f<,df/dt (2) 81 (2)
FRPFRQ3 f>/f<,df/dt (3) 81 (3)
FRPFRQ4 f>/f<,df/dt (4) 81 (4)
FRPFRQ5 f>/f<,df/dt (5) 81 (5)
FRPFRQ6 f>/f<,df/dt (6) 81 (6)
Overexcitation protection OEPVPH1 U/f> (1) 24 (1)
OEPVPH2 U/f> (2) 24 (2)
Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR1 3Ith>F (1) 49F (1)
Three-phase thermal overload protection, two time constants T2PTTR1 3Ith>T/G/C (1) 49T/G/C (1)
Negative-sequence overcurrent protection for machines MNSPTOC1 I2>M (1) 46M (1)
MNSPTOC2 I2>M (2) 46M (2)
Loss of phase (undercurrent) PHPTUC1 3I< (1) 37 (1)
PHPTUC2 3I< (2) 37 (2)
Loss of load supervision LOFLPTUC1 3I< (1) 37 (1)
LOFLPTUC2 3I< (2) 37 (2)
Motor load jam protection JAMPTOC1 Ist> (1) 51LR (1)
Motor start-up supervision STTPMSU1 Is2t n< (1) 49,66,48,51LR (1)
Phase reversal protection PREVPTOC1 I2>> (1) 46R (1)
Thermal overload protection for motors MPTTR1 3Ith>M (1) 49M (1)
Stabilized and instantaneous differential protection for machines MPDIF1 3dl>M/G (1) 87M/G (1)
High-impedance/flux-balance based differential protection for motors MHZPDIF1 3dIHi>M (1) 87MH (1)
Stabilized and instantaneous differential protection for two-winding transformers TR2PTDF1 3dI>T (1) 87T (1)
Numerical stabilized low-impedance restricted earth-fault protection LREFPNDF1 dIoLo> (1) 87NL (1)
LREFPNDF2 dIoLo> (2) 87NL (2)
High-impedance based restricted earth-fault protection HREFPDIF1 dIoHi> (1) 87NH (1)
HREFPDIF2 dIoHi> (2) 87NH (2)
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)
CCBRBRF2 3I>/Io>BF (2) 51BF/51NBF (2)
CCBRBRF3 3I>/Io>BF (3) 51BF/51NBF (3)
Three-phase inrush detector INRPHAR1 3I2f> (1) 68 (1)
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
TRPPTRC3 Master Trip (3) 94/86 (3)
TRPPTRC4 Master Trip (4) 94/86 (4)
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
High-impedance fault detection PHIZ1 HIF (1) HIZ (1)
Load-shedding and restoration LSHDPFRQ1 UFLS/R (1) 81LSH (1)
LSHDPFRQ2 UFLS/R (2) 81LSH (2)
LSHDPFRQ3 UFLS/R (3) 81LSH (3)
LSHDPFRQ4 UFLS/R (4) 81LSH (4)
LSHDPFRQ5 UFLS/R (5) 81LSH (5)
LSHDPFRQ6 UFLS/R (6) 81LSH (6)
Multipurpose protection MAPGAPC1 MAP (1) MAP (1)
MAPGAPC2 MAP (2) MAP (2)
MAPGAPC3 MAP (3) MAP (3)
MAPGAPC4 MAP (4) MAP (4)
MAPGAPC5 MAP (5) MAP (5)
MAPGAPC6 MAP (6) MAP (6)
MAPGAPC7 MAP (7) MAP (7)
MAPGAPC8 MAP (8) MAP (8)
MAPGAPC9 MAP (9) MAP (9)
MAPGAPC10 MAP (10) MAP (10)
MAPGAPC11 MAP (11) MAP (11)
MAPGAPC12 MAP (12) MAP (12)
MAPGAPC13 MAP (13) MAP (13)
MAPGAPC14 MAP (14) MAP (14)
MAPGAPC15 MAP (15) MAP (15)
MAPGAPC16 MAP (16) MAP (16)
MAPGAPC17 MAP (17) MAP (17)
MAPGAPC18 MAP (18) MAP (18)
Automatic switch-onto-fault logic (SOF) CVPSOF1 CVPSOF (1) SOFT/21/50 (1)
Voltage vector shift protection VVSPPAM1 VS (1) 78V (1)
Directional reactive power undervoltage protection DQPTUV1 Q> -> ,3U< (1) 32Q,27 (1)
DQPTUV2 Q> -> ,3U< (2) 32Q,27 (2)
Underpower protection DUPPDPR1 P< (1) 32U (1)
DUPPDPR2 P< (2) 32U (2)
Reverse power/directional overpower protection DOPPDPR1 P>/Q> (1) 32R/32O (1)
DOPPDPR2 P>/Q> (2) 32R/32O (2)
DOPPDPR3 P>/Q> (3) 32R/32O (3)
Three-phase underexcitation protection UEXPDIS1 X< (1) 40 (1)
UEXPDIS2 X< (2) 40 (2)
Low-voltage ride-through protection LVRTPTUV1 U<RT (1) 27RT (1)
LVRTPTUV2 U<RT (2) 27RT (2)
LVRTPTUV3 U<RT (3) 27RT (3)
Rotor earth-fault protection MREFPTOC1 Io>R (1) 64R (1)
High-impedance differential protection for phase A HIAPDIF1 dHi_A> (1) 87A (1)
High-impedance differential protection for phase B HIBPDIF1 dHi_B> (1) 87B (1)
High-impedance differential protection for phase C HICPDIF1 dHi_C> (1) 87C (1)
Circuit breaker uncorresponding position start-up UPCALH1 CBUPS (1) CBUPS (1)
UPCALH2 CBUPS (2) CBUPS (2)
UPCALH3 CBUPS (3) CBUPS (3)
Three-independent-phase non- directional overcurrent protection, low stage PH3LPTOC1 3I_3> (1) 51P-1_3 (1)
PH3LPTOC2 3I_3> (2) 51P-1_3 (2)
Three-independent-phase non- directional overcurrent protection, high stage PH3HPTOC1 3I_3>> (1) 51P-2_3 (1)
PH3HPTOC2 3I_3>> (2) 51P-2_3 (2)
Three-independent-phase non- directional overcurrent protection, instantaneous stage PH3IPTOC1 3I_3>>> (1) 50P/51P_3 (1)
Directional three-independent-phase directional overcurrent protection, low stage DPH3LPDOC1 3I_3> -> (1) 67-1_3 (1)
DPH3LPDOC2 3I_3> -> (2) 67-1_3 (2)
Directional three-independent-phase directional overcurrent protection, high stage DPH3HPDOC1 3I_3>> -> (1) 67-2_3 (1)
DPH3HPDOC2 3I_3>> -> (2) 67-2_3 (2)
Three-phase overload protection for shunt capacitor banks COLPTOC1 3I> 3I< (1) 51C/37 (1)
Current unbalance protection for shunt capacitor banks CUBPTOC1 dI>C (1) 51NC-1 (1)
Shunt capacitor bank switching resonance protection, current based SRCPTOC1 TD> (1) 55TD (1)
Control
Circuit-breaker control CBXCBR1 I <-> O CB (1) I <-> O CB (1)
CBXCBR2 I <-> O CB (2) I <-> O CB (2)
CBXCBR3 I <-> O CB (3) I <-> O CB (3)
Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
DCXSWI3 I <-> O DCC (3) I <-> O DCC (3)
DCXSWI4 I <-> O DCC (4) I <-> O DCC (4)
Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
ESXSWI2 I <-> O ESC (2) I <-> O ESC (2)
ESXSWI3 I <-> O ESC (3) I <-> O ESC (3)
Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
DCSXSWI4 I <-> O DC (4) I <-> O DC (4)
Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
ESSXSWI3 I <-> O ES (3) I <-> O ES (3)
Emergency start-up ESMGAPC1 ESTART (1) ESTART (1)
Autoreclosing DARREC1 O -> I (1) 79 (1)
DARREC2 O -> I (2) 79 (2)
Synchronism and energizing check SECRSYN1 SYNC (1) 25 (1)
Tap changer position indication TPOSYLTC1 TPOSM (1) 84M (1)
Tap changer control with voltage regulator OLATCC1 COLTC (1) 90V (1)
Condition monitoring and supervision
Circuit-breaker condition monitoring SSCBR1 CBCM (1) CBCM (1)
SSCBR2 CBCM (2) CBCM (2)
SSCBR3 CBCM (3) CBCM (3)
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Current circuit supervision CCSPVC1 MCS 3I (1) MCS 3I (1)
CCSPVC2 MCS 3I (2) MCS 3I (2)
Current transformer supervision for high-impedance protection scheme for phase A HZCCASPVC1 MCS I_A (1) MCS I_A (1)
Current transformer supervision for high-impedance protection scheme for phase B HZCCBSPVC1 MCS I_B (1) MCS I_B (1)
Current transformer supervision for high-impedance protection scheme for phase C HZCCCSPVC1 MCS I_C (1) MCS I_C (1)
Advanced current circuit supervision for transformers CTSRCTF1 MCS 3I,I2 (1) MCS 3I,I2 (1)
Fuse failure supervision SEQSPVC1 FUSEF (1) 60 (1)
Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1)
MDSOPT2 OPTS (2) OPTM (2)
Measurement
Three-phase current measurement CMMXU1 3I (1) 3I (1)
CMMXU2 3I (2) 3I (2)
Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
CSMSQI2 I1, I2, I0 (B) (1) I1, I2, I0 (B) (1)
Residual current measurement RESCMMXU1 Io (1) In (1)
RESCMMXU2 Io (2) In (2)
Three-phase voltage measurement VMMXU1 3U (1) 3V (1)
Single-phase voltage measurement VAMMXU2 U_A (2) V_A (2)
VAMMXU3 U_A (3) V_A (3)
Residual voltage measurement RESVMMXU1 Uo (1) Vn (1)
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1)
Load profile record LDPRLRC1 LOADPROF (1) LOADPROF (1)
Frequency measurement FMMXU1 f (1) f (1)
Fault location
Fault locator SCEFRFLO1 FLOC (1) 21FL (1)
Power quality
Current total demand distortion CMHAI1 PQM3I (1) PQM3I (1)
Voltage total harmonic distortion VMHAI1 PQM3U (1) PQM3V (1)
Voltage variation PHQVVR1 PQMU (1) PQMV (1)
Voltage unbalance VSQVUB1 PQUUB (1) PQVUB (1)
Other
Minimum pulse timer (2 pcs) TPGAPC1 TP (1) TP (1)
TPGAPC2 TP (2) TP (2)
TPGAPC3 TP (3) TP (3)
TPGAPC4 TP (4) TP (4)
Minimum pulse timer (2 pcs, second resolution) TPSGAPC1 TPS (1) TPS (1)
TPSGAPC2 TPS (2) TPS (2)
Minimum pulse timer (2 pcs, minute resolution) TPMGAPC1 TPM (1) TPM (1)
TPMGAPC2 TPM (2) TPM (2)
Pulse timer (8 pcs) PTGAPC1 PT (1) PT (1)
PTGAPC2 PT (2) PT (2)
Time delay off (8 pcs) TOFGAPC1 TOF (1) TOF (1)
TOFGAPC2 TOF (2) TOF (2)
TOFGAPC3 TOF (3) TOF (3)
TOFGAPC4 TOF (4) TOF (4)
Time delay on (8 pcs) TONGAPC1 TON (1) TON (1)
TONGAPC2 TON (2) TON (2)
TONGAPC3 TON (3) TON (3)
TONGAPC4 TON (4) TON (4)
Set-reset (8 pcs) SRGAPC1 SR (1) SR (1)
SRGAPC2 SR (2) SR (2)
SRGAPC3 SR (3) SR (3)
SRGAPC4 SR (4) SR (4)
Move (8 pcs) MVGAPC1 MV (1) MV (1)
MVGAPC2 MV (2) MV (2)
MVGAPC3 MV (3) MV (3)
MVGAPC4 MV (4) MV (4)
Integer value move MVI4GAPC1 MVI4 (1) MVI4 (1)
MVI4GAPC2 MVI4 (2) MVI4 (2)
MVI4GAPC3 MVI4 (3) MVI4 (3)
MVI4GAPC4 MVI4 (4) MVI4 (4)
Analog value scaling SCA4GAPC1 SCA4 (1) SCA4 (1)
SCA4GAPC2 SCA4 (2) SCA4 (2)
SCA4GAPC3 SCA4 (3) SCA4 (3)
SCA4GAPC4 SCA4 (4) SCA4 (4)
Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1)
SPCGAPC2 SPC (2) SPC (2)
SPCGAPC3 SPC (3) SPC (3)
Remote generic control points SPCRGAPC1 SPCR (1) SPCR (1)
Local generic control points SPCLGAPC1 SPCL (1) SPCL (1)
Generic up-down counters UDFCNT1 UDCNT (1) UDCNT (1)
UDFCNT2 UDCNT (2) UDCNT (2)
UDFCNT3 UDCNT (3) UDCNT (3)
UDFCNT4 UDCNT (4) UDCNT (4)
UDFCNT5 UDCNT (5) UDCNT (5)
UDFCNT6 UDCNT (6) UDCNT (6)
UDFCNT7 UDCNT (7) UDCNT (7)
UDFCNT8 UDCNT (8) UDCNT (8)
UDFCNT9 UDCNT (9) UDCNT (9)
UDFCNT10 UDCNT (10) UDCNT (10)
UDFCNT11 UDCNT (11) UDCNT (11)
UDFCNT12 UDCNT (12) UDCNT (12)
Programmable buttons (16 buttons) FKEYGGIO1 FKEY (1) FKEY (1)
Logging functions
Disturbance recorder RDRE1 DR (1) DFR (1)
Fault recorder FLTRFRC1 FAULTREC (1) FAULTREC (1)
Sequence event recorder SER1 SER (1) SER (1)