CTRL.ESXSWI1 Earthing switch control (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023

620 series DNP3 Point List Manual

Table 1. CTRL.ESXSWI1 Earthing switch control (1)
IEC 61850 name SA name Description Values
CTRL.ESCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByps.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked