CTRL.ESXSWI1 Earthing switch control (1) - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 22.05.2023
620 series DNP3 Point List Manual
Table 1. CTRL.ESXSWI1 Earthing switch control (1)
| IEC 61850 name |
SA name |
Description |
Values |
| CTRL.ESCILO1 |
|
|
|
| .EnaCls.stVal |
ENA_CLOSE |
Close enabled |
1=Enabled |
| .EnaOpn.stVal |
ENA_OPEN |
Open enabled |
1=Enabled |
| .ItlByps.stVal |
ITL_BYPASS |
Interlocking bypass |
1=Bypassed |
| CTRL.ESCSWI1 |
|
|
|
| .Pos.stSeld |
SELECTED |
CB selected |
1=Selected |
| CTRL.ESXSWI1 |
|
|
|
| .BlkCls.stVal |
BLK_CLOSE |
Close blocked |
1=Blocked |
| .BlkOpn.stVal |
BLK_OPEN |
Open blocked |
1=Blocked |