Analog inputs - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Power management/Load shedding - DNP3 Communication Manual - 620 series Relion Protection and Control - Relion Protection and Control - 2.0 FP1 IEC - IEC - 28.04.2023

620 series DNP3 Point List Manual

Table 1. Explanations of the analog input table columns
Column name Description
IEC 61850 name Original IED data object identification. Described in the IEC 61850 format as Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Values The value range of the original IEC 61850 data. Scaling is needed to convert floating point data into DNP3 integer values.
S Scaling type selected as default. Default “R” means ratio scaling. See the DNP3 communication protocol manual for details.
Arg 1, 2, 3, 4 Scaling argument values as default. When ratio scaling is selected, the four values correspond to min value in, max value in, min value out, and max value out. See the DNP3 communication protocol manual for details.