Time synchronization - Arc protection - Merging unit - Motor protection - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Interconnection protection - Busbar differential protection (high impedance) - Generator protection - Power management/Load shedding - Back-up protection - IEC 60870-5-103 Communication Manual - 615 series Relion Protection and Control - 5.0 FP1 IEC - IEC - 22.05.2023

615 series IEC 60870-5-103 Communication Protocol Manual

Time synchronization over IEC 60870-5-103 is supported. This requires that the IED’s global Time Sychronization Source parameter (in Configuration > Time > Synchronization > Synch source) is set to "IEC 60870-5-103" mode. If some other time synchronization source is configured for the IED, the IEC 60870-5-103 time synchronization messages are rejected.