Class 2 frame 6
This frame is equal in all relays of this series. It contains pre-defined mappings to most of the measurands present in the product series. In case the relay configuration does not contain some of the measurands of Class 2 frame 6, then the corresponding values are set as constant 0. Trailing 0 values are cut from the frame and the frame becomes shorter. The default function type/information number definitions for frame 6 are FUN = 10, INF = 236.
Class 2 frame 7
This frame may be selected, but it is currently empty. The default function type/information number definitions for frame 7 are FUN = 10, INF= 237.
| Frame number | ASDU | FUN | INF | Num of data | Data in Class 2 frame |
|---|---|---|---|---|---|
| 6 | 9 | 10 | 236 | 21 (max) | IL1, IL2, IL3, Io, UL1, UL2, UL3, U12, U23, U31, Uo, P, Q, Pf, Freq, SeqCurrent [Pos,Neg,Zro], SeqVoltage [Pos,Neg,Zro] |
| 7 | 9 | 10 | 237 | 0 | - |
User-definable Class 2 frame 0
As a third option, an own private Class 2 frame can freely be composed using PCM600. The function type and information number can also be configured for this user-definable Class 2 frame through the setting parameters UsrFType n and UsrInfNo n via . Default values are FUN = 10, INF = 230.
See the list of available measurands from the product-specific point list manuals.