Energy counters - Arc protection - Merging unit - Motor protection - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Interconnection protection - Busbar differential protection (high impedance) - Generator protection - Power management/Load shedding - Back-up protection - IEC 60870-5-103 Communication Manual - 615 series Relion Protection and Control - 5.0 FP1 IEC - IEC - 22.05.2023

615 series IEC 60870-5-103 Communication Protocol Manual

Counters are not defined by the IEC 60870-5-103 standard in general. A private data unit ASDU 205 is used to define counters. All IEC 60870-5-103 masters does not support this non-standard ASDU type.

Table 1. ASDU 205 Class1 event message outlook
Octets Description
205 Type ID
0×81 VSQ (= one data)
1 COT (= spontaneous)
Addr Unit address
FUN Function type
INF Information number
LSB Counter value
:
:
MSB
[ms] Time stamp
[min]
[hour]
Table 2. Counter value outlook in detail
Octet Description
1 Bits 0...7 = Counter bits 0…7
2 Bits 0…7 = Counter bits 8…15
3 Bits 0…7 = Counter bits 16..23
4 Bits 0…3 = Counter bits 24...27, Bit 4= sign, Bits 5...7 = Not used

In practice only the energy values from the internal PEMMTR function are pre-mapped into ASDU 205 values.

Table 3. ASDU 205 pre-mapped values
IEC 61850 object Description FUN INF
LD0.PEMMTR1.SupWh.actVal Reversed active energy 133 51
LD0.PEMMTR1.SupVArh.actVal Reversed reactive energy 133 52
LD0.PEMMTR1.DmdWh.actVal Forward active energy 133 53
LD0.PEMMTR1.DmdVArh.actVal Forward reactive energy 133 54