Class 2 measurands - Arc protection - Merging unit - Motor protection - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Interconnection protection - Busbar differential protection (high impedance) - Generator protection - Power management/Load shedding - Back-up protection - IEC 60870-5-103 Communication Manual - 615 series Relion Protection and Control - 5.0 FP1 IEC - IEC - 22.05.2023

615 series IEC 60870-5-103 Communication Protocol Manual

The interchangeable part of the IEC 60870-5-103 standard defines that only five Class 2 measurands frames exist. Measurands transmitted in these five Class 2 frames relates to current and voltage values only. The allowed scale factors, actually meaning |max values| of per unit coded measurands, are 1.2 or 2.4. The IEDs support all five interchangeable Class 2 measurand frames defined by the standard.

Table 1. Interchangeable Class 2 measurand frames
Frame number ASDU FUN INF Num of data Data in the Class 2 frame
1 3 0 144 1 IL2
2 3 0 145 2 IL2, U12
3 3 0 146 4 IL2, U12, P3, Q3
4 3 0 147 2 Io, Uo
5 9 0 148 9 IL1, IL2, IL3, UL1, UL2, UL3, P3, Q3, f
1 FUN = 0 means that the Function type is coded as the Device function type which in turn is defined by the setting parameter DevFunType n.