Troubleshooting - Arc protection - Merging unit - Motor protection - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Interconnection protection - Busbar differential protection (high impedance) - Generator protection - Power management/Load shedding - Back-up protection - DNP3 Communication Manual - 615 series Relion Protection and Control - Relion 615 series - 5.0 FP1 IEC - IEC - 22.05.2023

615 series DNP3 Communication Protocol Manual

Table 1. Troubleshooting
Condition Cause Remedy
Slow or no update of data, reports disabled

Protocol data is available for active IED applications and the IED system. Active IED applications mean the function blocks that have been added into the protection relay's configuration using the Application Configuration in PCM600. The IED system data is always available and is not dependent on the application configuration.

A protection relay variant has a standard application configuration that has been done in advance. This configuration can be modified with PCM600. It is also possible to start a completely new configuration from an emptied configuration state in Application Configuration. When a new IED configuration is created from an empty configuration state, an additional PCM600 check must be done at the end.

Select manually the check boxes for clients of all visible 61850 data sets in the IEC 61850 Configuration tool, see the engineering guide for detailed instructions. This procedure enables reporting for the data sets, and report control blocks should appear on the Report Control tab.