Communication modes - Arc protection - Merging unit - Motor protection - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Interconnection protection - Busbar differential protection (high impedance) - Generator protection - Power management/Load shedding - Back-up protection - DNP3 Communication Manual - 615 series Relion Protection and Control - 5.0 FP1 IEC - IEC - 27.04.2023

615 series DNP3 Communication Protocol Manual

DNP3 communication can be set up in two alternative modes.

  • Polled mode, also called “polled report by exception”. In this mode the DNP3 client always initiates the transaction with a read or write request to the DNP3 server. The server must reply with a response message.
  • Unsolicited mode, called also “Unsolicited reporting mode”. In this mode the DNP3 server may spontaneously send changed class events to the client. The client can yet make additional read or write requests to the server.

By default, DNP3 operates in polled mode. Unsolicited reporting mode can be activated with the UR mode parameter.